Who Makes Cutler-Hammer and Westinghouse Breakers Now?
Eaton does. Eaton acquired the Cutler-Hammer business and, in 1994, took over Westinghouse's electrical distribution and control business. It consolidated those legacy molded-case lines into what is now the Eaton Series C family, and it has since folded the Cutler-Hammer name into the Eaton brand.
For a plant engineer, the key point is that the OEM lineage is unbroken. There is an official successor for almost every legacy frame, and Series C breakers were designed to fit many existing Westinghouse and Cutler-Hammer panelboards and switchboards. A discontinued breaker usually does not force a whole-panel replacement. You cross-reference to the current Series C equivalent, or you source the original. Browse our circuit breakers in stock when you are ready.
Find the frame letter, look up the Series C frame in the chart below, then confirm amperage, interrupting rating, trip type, poles and voltage, and mounting before you order.
Cutler-Hammer / Westinghouse to Eaton Series C Cross-Reference
Navigating the legacy catalog comes down to the frame letter and the ampere rating. Eaton carried the same frame letters forward: an old F-frame becomes an Eaton FD, a K-frame becomes a KD, and so on. An "H" prefix denotes a higher interrupting rating (FD versus HFD, KD versus HKD). Use the frame letter to find your row, then confirm the exact rating.
| Legacy Westinghouse / Cutler-Hammer Frame (Examples) | Eaton Series C Equivalent |
Amp Range (Typical) and Trip / Notes |
|---|---|---|
| E-frame (e.g., EB, EHB) | E-frame (EGB, GHB) | 15–125 A, thermal-magnetic |
| F-frame (e.g., FB, HFB) | F-frame (FD / FDB / HFD) | 15–225 A, "H" prefix = higher interrupting rating |
| J-frame (e.g., JA, JB) | J-frame (JD / HJD) | Up to 250 A, thermal-magnetic |
| K-frame (e.g., KA, KB, HKB) | K-frame (KD / HKD) | Up to 400 A, thermal-magnetic |
| L-frame (e.g., LA, LB, HLB) | L-frame (LD / HLD) |
Up to 600 A, thermal-magnetic or Digitrip |
| M-frame (e.g., MA, MB) | M-frame (MDL) | Up to 800 A, Digitrip electronic trip |
| N-frame (e.g., NA, NB) | N-frame (ND / NB) | Up to 1200 A, Digitrip electronic trip |
| R-frame | R-frame (RD) | 1600–2500 A, Digitrip RMS electronic trip |
The designators and example part numbers above are a starting map, not a finished part number. The exact Series C catalog number also depends on interrupting rating, poles, and trip type. Verify against Eaton's current cross-reference, or send us the legacy number and we will return the exact match.
The Five Checks That Turn a Frame Into a Part Number
The chart tells you which Series C frame to look at. To land on the correct part number, match these five items:
The frame sets the ceiling. You still specify the trip rating within it.
Legacy breakers came in standard and high-interrupting versions. Match or exceed the available fault current at your voltage. An "H" prefix Series C frame is the higher-interrupting option.
Smaller frames are thermal-magnetic, while larger L, M, N, and R frames often use Digitrip electronic trip units. Replicate the behavior you have.
Confirm 2-, 3-, or 4-pole construction and the system voltage.
Confirm fixed, plug-in, or drawout mounting, lug type, and any shunt trips, auxiliary contacts, undervoltage releases, or handle mechanisms.
Get any one of these wrong and the breaker may fit but protect the circuit incorrectly. If you would rather not chase all five, send us the legacy catalog number and we will return the exact Eaton Series C match.
Common Cross-Reference Mistakes
The breaker frame alone is not a complete part number; it only narrows the search. Always verify the interrupting rating, as standard and high-interrupting versions are not interchangeable. Also, avoid swapping trip types, since replacing a Digitrip electronic unit with a basic thermal-magnetic breaker can change the equipment's protection behavior.
Check all accessories, including shunt trips, auxiliary contacts, and undervoltage releases, to ensure they are properly accounted for. Remember that physical fit does not guarantee a listed or approved combination, and never reconstruct a catalog number using incomplete or worn nameplate markings.
A cross-reference is a starting point, not an approval. Physical fit does not equal code, UL, or AHJ acceptance. Always confirm the exact rating and installation against the equipment nameplate and your local Authority Having Jurisdiction before energizing.
The Five Checks That Turn a Frame Into a Part Number
The chart tells you which Series C frame to look at. To land on the correct part number, match these five items:
- Exact ampere rating. The frame sets the ceiling. You still specify the trip rating within it.
- Interrupting rating (kAIC). Legacy breakers came in standard and high-interrupting versions. Match or exceed the available fault current at your voltage. An "H" prefix Series C frame is the higher-interrupting option.
- Trip type. Smaller frames are thermal-magnetic, while larger L, M, N, and R frames often use Digitrip electronic trip units. Replicate the behavior you have.
- Poles and voltage. Confirm 2-, 3-, or 4-pole construction and the system voltage.
- Mounting, connections, and accessories. Confirm fixed, plug-in, or drawout mounting, lug type, and any shunt trips, auxiliary contacts, undervoltage releases, or handle mechanisms.
When a Cross-Reference Needs a Second Look
Slow down and verify further in these situations:
- The nameplate is worn, painted over, or unreadable
- The breaker uses a Digitrip electronic trip unit with custom settings
- Available fault current is unknown or has changed
- The breaker is drawout, or has several accessories
- The equipment is a loadcenter rather than industrial gear
- The panel also contains fused switches, so you may want to review safety switches
Common Cross-Reference Mistakes
- Treating the frame as a finished part number. The frame only narrows the search.
- Ignoring the interrupting rating. Legacy standard and high-interrupting versions are not interchangeable.
- Swapping trip types. Replacing a Digitrip electronic unit with a basic thermal-magnetic breaker changes protection behavior.
- Overlooking accessories. Shunt trips, auxiliary contacts, and undervoltage releases have to be carried over.
- Assuming a physical fit means approval. A breaker that merely fits the bus is not automatically a listed or approved combination.
- Guessing from a worn nameplate. Never rebuild a catalog number from partial characters.
Get any one of these wrong and the breaker may fit but protect the circuit incorrectly. If you would rather not chase all five, send us the legacy catalog number and we will return the exact Eaton Series C match.
Have a discontinued Cutler-Hammer loadcenter instead? If you are holding an old residential or light-commercial loadcenter rather than industrial gear, the path is different from the molded-case cross-reference above. Legacy Cutler-Hammer Type CH and Type BR loadcenters each take their own breaker line, and Eaton Type BR breakers are also UL-listed for certain legacy Westinghouse, Challenger, and Bryant loadcenters. Eaton publishes details on its Classified Circuit Breakers page.
The deadfront or door is marked with the breaker types the panel accepts, for example "Use Type BR." Match that listing exactly and confirm with your local AHJ. A breaker that merely fits the bus is not automatically a listed, approved combination.
Photographing the Breaker Before Sourcing
Clear photos let a supplier identify the breaker quickly. The frame letter leads the catalog number (E, F, J, K, L, M, N, or R), sometimes with an interrupting prefix such as "H," and the characters that follow indicate poles and ampere rating.
When documenting a breaker, capture:
- Complete catalog number and frame letter
- Ampere rating, voltage, and number of poles
- Overlooking accessories. Shunt trips, auxiliary contacts, and undervoltage releases have to be carried over.
- Interrupting rating
- Trip unit face and settings
- Accessory markings
- Equipment nameplate
- Front, side, and rear views where safely accessible
If the nameplate is worn or painted over, do not guess. Send us a photo and we will identify it. Only qualified persons should work near energized equipment.
Three Ways to Solve a Discontinued Breaker
| Option | Best When | What to Confirm |
|---|---|---|
| Cross-reference to Eaton Series C | You are comfortable moving to the successor part | Frame, ratings, trip type, accessories |
| Source a new-surplus or obsolete original | Documentation, spares standardization, or a fleet of matching panels favors an exact original | Catalog number, condition |
| Modernize the gear | A larger upgrade is already planned | Panelboard or switchboard replacement scope |
Option three is usually unnecessary given Series C's backward compatibility. We can cross-reference the Eaton Series C part or supply the original from inventory, so one failed breaker does not turn into a full gear replacement. For help with condition terms, see our Square D I-Line breaker replacement guide, which covers a similar process for another legacy line.
What to do next
Before requesting a quote, gather the legacy catalog number or a clear nameplate photo, frame letter, interrupting prefix, ampere rating, voltage, number of poles, trip type, and settings. Also, note the mounting style, accessories, equipment nameplate, and panel label.
Include the required quantity, condition (new, new-surplus, reconditioned, or used), ship-to location, and required-by date. For related replacement research, read our Crouse-Hinds breaker replacement guide or consult UL Solutions for listing and classification questions.
Send us the nameplate and we'll read it for you
Have a discontinued Cutler-Hammer or Westinghouse breaker? Send us the catalog number or a nameplate photo and we will match the exact Eaton Series C part, or supply a new, new-surplus, or obsolete original from our inventory. Orders placed before 12 PM EST ship the same day.
Frequently asked
Eaton does. Eaton acquired Cutler-Hammer, took over Westinghouse's electrical distribution business in 1994, and now sells these lines under the Eaton brand.
In most cases it is the Eaton Series C breaker in the same frame letter, for example an F-frame becoming an FD. Confirm the exact amperage, interrupting rating, trip type, and poles before ordering.
Series C breakers were designed to fit many existing Westinghouse and Cutler-Hammer panelboards and switchboards. Check the exact model, panel nameplate, and local AHJ requirements rather than assuming.
Many legacy frames and catalog numbers are. Send us the number or a nameplate photo and we will confirm its status and the current equivalent.
Often yes. We supply new-surplus and obsolete originals from inventory, which keeps an existing installation identical.